Duplex™ II General Description

The Duplex System allows for the automatic control and operation of up to two Eclipse actuators. During an emergency closure, the Duplex Model II will close up to 2 Eclipse actuators automatically and sequentially. The Duplex Model II meets all Fire Code requirements.

Remote Operation Automatically shut-off a leak without having to enter a toxic environment by means of remote switches: gas detector, kill or panic button, SCADA system, fire or seismic alarm, etc..

Features:

  • Electronically Closes Valves - Approx. 3/4 sec!
  • LED System Information Display Allows Multiple Remote Switches
  • Fault Error Diagnostic System
  • Battery Operated (3 days w/AC failure)
  • 2 Levels of Torque: Emergency - 50 ft. lbs. Test - 30 ft. lbs.
  • Fits Standard Valve Configurations
  • Operator can Open / Close valve manually
  • Microprocessor Controlled
  • Entire System NEMA-4X
  • 3-Way Over Torque Protection
  • 3 Year Warranty

Duplex II Technical Specs

Controller Model : 6503.01
Channels : Up to 2 Actuators
Enclosure Dimensions : 14.705x 12.125 x 8.31 inches (373 x 308 x 211 mm)
Enclosure Weight : 14.5 lbs (6.5 kgs)
Battery Weight : 7 lbs (3.2 kgs)
Enclosure Rating : NEMA 4X / IP66
Temperature Range : -10 C to 50 C
Display : 2 line 40 charachter backlit OLED
Power Requirement : 120 - 240 VAC
Power Use : 100 watts
Current : 0.9A @ 120 VAC
Relay Contact Rating : 0.2A @ 24 VDC
Charger : Constant voltage trickle charge
Battery Backup : 3 days, 8.5 amp hour
Emergency Stop Button : Normally Open contact (Optional N.C. Contact)
Warranty : 3 Years
Optional Relay Contacts: (3) per relay card, 5A @ 120 VAC ea.
Optional SCADA Output : RS-232 output of 9 system diagnostics
Accessories : Actuator storage rack (1 per actuator)

 

 

 

 

 

 

Duplex II Options

  • RS232 Serial Port Output to SCADA
  • Fault Error Output Relay
  • DT-DP Relay (Latching available)
  • Annual Preventative Maintenance Program

 

 

 

 

 

 

 

 

 

 

 

 

Duplex II is compatible with the following Actuators:

 

Eclipse Actuator Eclipse XP Actuator
Eclipse Actuator Eclipse XP Actuator

Duplex II Brochures

 

 

 

Duplex II Controller


The Duplex II controller allows operators to remotely close 1 or 2 chlorine or sulfur dioxide valves in an emergency situation.


Bulletin 903

Optional Relay Interface Module
for Duplex II Controller

The optional Relay Interface Module (RIM) for the Duplex II Controller provides three dry contact output relays rated 5A @ 250VAC.

Bulletin 903.A

 

  • Force Flow